The difference between chilled water and DX comes down to what carries the cooling through the building: chilled water systems pipe cold water from a central chiller, while direct-expansion (DX) systems run refrigerant straight to a coil in each unit. DX is simpler and cheaper to buy for most small and mid-size buildings. Chilled water costs more up front but can be more efficient and easier to manage in large buildings or campuses with a lot of cooling load in one place.
Here's how each works, where each fits, and where geothermal comes in.
How a DX system works
In a DX system, the refrigerant itself does the cooling at the air handler. A compressor pumps refrigerant to a coil in the airstream. The refrigerant boils inside the coil, pulls heat out of the air passing over it, and carries that heat back to a condenser that rejects it outdoors.
The most common DX equipment in commercial buildings is the packaged rooftop unit, which puts the compressor, coil, fan and controls in one box on the roof. The Department of Energy has estimated that rooftop units cool about 60% of U.S. commercial floor space. Split systems, with an indoor air handler connected by refrigerant lines to an outdoor condensing unit, are DX too.
How a chilled water system works
A chilled water system adds a step. A central chiller cools water, and pumps send that water through pipes to air handlers and fan coils across the building. Each air handler has a water coil instead of a refrigerant coil. The warmed water returns to the chiller, and the chiller rejects the heat outside.
Chillers reject heat in one of two ways:
- Air-cooled chillers use outdoor fans, like a large condensing unit. They sit outside or on the roof.
- Water-cooled chillers sit indoors and send their heat to a cooling tower through a second water loop, called condenser water.
The Department of Energy's Federal Energy Management Program notes that air-cooled chillers avoid the need for a cooling tower but are substantially less efficient than water-cooled chillers.
The main differences
| DX (rooftop units, splits) | Chilled water | |
|---|---|---|
| What moves the cooling | Refrigerant, to each unit's coil | Water, from a central plant to every coil |
| Equipment | Many self-contained units | Chillers, pumps, piping, air handlers, often a cooling tower |
| First cost | Lower for most small and mid-size buildings | Higher, with a central plant and piping |
| Where equipment sits | Mostly on the roof or outside | Mostly in a mechanical room, with a tower or air-cooled chiller outside |
| Maintenance | Spread across many units | Concentrated in one plant, plus water treatment |
| If one unit fails | One zone loses cooling | Depends on how many chillers and pumps are installed as backup |
Efficiency
Large chillers are rated in kilowatts per ton, where a lower number is better. FEMP's federal purchasing requirements show how efficiency improves with size. For full-load-optimized water-cooled centrifugal chillers, the requirement is 0.610 kW per ton for units under 150 tons and 0.501 kW per ton for units of 600 tons and up. FEMP also requires chillers to meet a part-load rating, because most chillers spend most of their hours below full capacity.
That's part of why central plants make sense in big buildings: one large, efficient machine running a whole campus can beat dozens of small compressors. But it only holds up if the plant is designed and run well. Pumps, the cooling tower and the controls all use energy too, and a poorly controlled chiller plant can give away its advantage.
DX equipment has improved a lot, and for a typical office, church or single school building, well-chosen rooftop units are often the most practical answer. Where the line falls between the two depends on the building's size, layout, hours and how much cooling it needs at one time. An engineer's load calculation, not a rule of thumb, should settle it.
Maintenance and water treatment
A DX building has many units to maintain, each with its own compressor, refrigerant circuit and filters. The work is routine, but it's spread across the roof.
A chilled water building concentrates the work in the plant: chiller service, pump maintenance, valve and coil checks, and water treatment for the chilled water loop. A water-cooled plant adds a cooling tower, which needs regular cleaning and chemical treatment. The CDC lists cooling towers among the building devices that should be cleaned, disinfected and maintained under the manufacturer's instructions to control Legionella, the bacteria behind Legionnaires' disease, and says buildings at increased risk should have a water management program. If you're weighing a water-cooled plant, budget for that program from day one.
Which fits your building
DX usually fits when:
- The building is small to mid-size, or spread out in separate wings
- Zones run on different schedules, like a church with a sanctuary used a few times a week
- There's no room for a mechanical plant, or no staff to run one
- The budget favors lower first cost and simple replacement
Chilled water usually fits when:
- The building or campus is large and the cooling load is concentrated
- There's already a central plant and piping worth keeping
- The owner wants less equipment on the roof
- Long operating hours make efficiency gains add up
- The building already uses VAV air handlers fed by chilled water
Many buildings use both: a chilled water plant for the main building and DX units for an addition, a gym or a server room.
Where geothermal fits
Geothermal isn't a third category so much as a different heat source and heat sink. Instead of rejecting heat to outdoor air or a cooling tower, a geothermal system trades heat with water circulating through a well field in the ground. Here's how that works.
It can look like either system:
- Like DX. Water-to-air heat pumps in each zone, each with its own small refrigerant circuit, all connected to the ground loop. This setup can replace rooftop units with indoor equipment.
- Like chilled water. Water-to-water heat pumps make chilled water in summer and hot water in winter and feed the building's existing air handlers. This setup can replace a chiller, cooling tower and boiler with heat pumps and a well field.
If your cooling tower is near the end of its life, a geothermal well field can take its place as the heat sink. Our cooling tower replacement guide covers how to tell when a tower is done. For schools, churches and other nonprofits, the federal credit for geothermal comes back as a cash payment, which changes how the options compare.
Next step
Fischer Mechanical installs chilled water systems, split systems, rooftop units and geothermal systems for commercial buildings in the St. Louis area. If you're deciding between them, request a free estimate or call 636-327-4238. To see how geothermal compares with a conventional price, try the geothermal calculator.